GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

Table 9-4: BCM Standard Holding Register Address Mapping (Continued)

Modbus

Data

Address

Menu Item

Units and Range

Default/(Comm

ents)

OPERATING DATA REGISTERS (Continued)

2n10

BMM #0 Capacity

(n = 0 – 7)

0 – 255 kW

(Read Only)

2n11

BMM #n Configuration

(n = 0 – 7)

Flag (0, 1)

0: Space Heating Only

1: Space Heating and DHW

(Read Only)

2n20

BMM #n Operating Flags (n =

0 – 7)

Flags (0-255)

Bit 3: Flame detected

Bit 4: Check mode

Bit 6: Pump status

Bit 7: Alarm

(Read Only)

SYSTEM DATA

1550

Firmware Code & Firmware

Revision

0x3400 – 0x34FF

High byte: Firmware Code

Low byte: Firmware Revision

(Read Only)

1011

Boiler Global Capacity

0 – FFFF kW

(Read Only)

12

Boiler Mode = AERCO BMS

II/ACS

2

(Read Only)

13

Remote Signal = Network

3

(Read Only)

SETTINGS

19

Modbus Address

1 - 127

(Read/Write)

3000

Burner OFF Hysteresis

9°F to 36°F (5°C to 20°C)

(Value x 10)

(Read/Write)

9°F

3001

Minimum Inserted Burner

1 - 8

(Read/Write) 1

3002

Temp. Control: Slope Limit

2°F to 54°F/minute (1°C to

30°C/minute)

(Read/Write) 9°F

3003

Temp. Control: Proportional

Band

0°F to 90°F (0°C to 50°C)

(Read/Write) 45°F

3004

Temp. Control: Integral Gain

0 - 50

(Read/Write) 12

3005

Temp. Control:

Derivative Gain

0 - 50

(Read/Write) 12

3006

Pump Over-run Time

1 – 10 minutes

(Read/Write) 5 min.