Gf-115-c, Modulex e8 controller and bcm – AERCO Modulex E8 Controls Guide User Manual

Page 88

Advertising
background image

PR1: 11/30/12

Page

88 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

Table 8-4: EXPERT Menu Sub-Menus and Parameters (Continued)

FUNCTION

DESCRIPTION

ENTRY RANGE DEFAULT

HEAT CIRCUIT 1 & 2 Sub-Menus (Continued)

B-HEAT SINK

Circuit Enable

00 = OFF

01 = ON

01 (ON)

RETURN

Press Program Key to exit HEAT

CIRCUIT 1 (or 2) Sub-Menu.

SOLAR M/F Sub-Menu

MF (1-4)

FUNCTION

Multi-Function (MF) Relay Functions.
00 = No Function

01 = Header Pump

02 = Circulation (Time)

03 = Booster Pump

05 = Pump HS1

06 = Pump HS2

20 = Temp-Controlled Circulation Pump

21 = Pulsed Circulation Pump

22 = Solid Fuel Boiler Integration

23 = Solar Integration

24 = Return Flow Temperature Increase

HS1

25 = Return Flow Temperature Increase

HS2

26 = Return Flow Temperature Increase

HS

Via Buffer Storage

00, 01, 02, 03,

05, 06 & 20-26

00

(No

Function)

MF (1-4)

SET TEMP

Multi-Function Relay Set Point

Temperature

indicates switching temperature for relay

86F – 194F

86°F

MF (1-4)

HYST (1-4)

Multi-Function Relay Hysteresis

39°F – 64°F

48°F

F15 FUNCTION

F15 Function

00 = Room Sensor for Heating Circuit 2

01 = 0 – 10V iInput

02 = Light sensor

00 -02

00

RETURN

Press Program Key to exit SOLAR M/F

Sub-Menu.




Advertising