5.4.3 Setting the DHW Set Point

The set point temperature is set in the USER menu as shown in instructions below.

NOTE

Typically,

a higher water temp is needed to heat domestic hot

water to its setpoint. Do this by using

EXPERT / HOT WATER / T

BOILER DHW. Degrees entered are added to DHW Setpoint in

USER

MENU. See paragraph 5.2.3.

Setting the DHW Set Point

1.

Use Rotary Knob to scroll to

USER menu and INSTALLATION sub-menu.

2.

Continue scrolling clockwise until the

HOT WATER sub-menu is displayed.

3.

Press the Program Key to enter the

HOT WATER sub-menu.

4.

Scroll to

T-DHW 1, displayed along with the current DHW set point temperature.

5.

To change

DHW set point, press the Program Key. Red LED will light.

6.

Using the Rotary Knob, enter the desired set point temperature.

7.

With desired DHW set point displayed, press Program Key to save. The red LED will go off.

8.

Continue scrolling until

RETURN is displayed. Press Program Key to exit.

9.

Scroll clockwise to the

EXPERT menu, HOT WATER sub-menu.

10.

Press Program Key and scroll to the

T BOILER DHW in HOT WATER sub-menu. Current

value is displayed in °F.

11.

To change temp, press Program Key to enter value that will be added to the

DHW set point.

Red LED lights.

12.

Adjust the

T BOILER DHW temperature to desired value using the Rotary Knob.

13.

Press Program Key to store the temp setting. The red LED will go off.

14.

Continue scrolling through the

HOT WATER sub-menu until RETURN is displayed. Press

the Program Key to exit the sub-menu.