Gf-115-c, Modulex e8 controller and bcm – AERCO Modulex E8 Controls Guide User Manual

Page 31

Advertising
background image

PR1: 11/30/12

Page

31 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

Table 4-3: EXPERT Menu Listing (Continued)

FUNCTION

DESCRIPTION

ENTRY

RANGE

DEFAULT

SOLAR M/F Sub-Menu

MF (1-4)

FUNCTION

Not Applicable

MF (1-4)

SET TEMP

Not Applicable

MF (1-4)

HYST (1-4)

Not Applicable

F15 FUNCTION

F15 Function

00 = Room Sensor for Heating Circuit 2

01 = 0 – 10V iInput

02 = Light sensor

00 -02

00

RETURN

Press Program Key to exit SOLAR M/F

Sub-Menu.


4.4.1 Available V-Curve Preset Voltage Curves for 0 – 10 Volt Input

The following listing (

Table 4-4) shows the available preset V-Curve settings for operation in

the 0 to 10 Volt Mode:

Table 4-4: V-Curve Preset Voltage Curves for 0 – 10 Volt Input

CURVE NO.

U1

U2

T1

T2

UO

0

2.0 V

10.0 V

32°F

194°F

2.0 V

1

2.5 V

0.3 V

100°F

176°F

5.0 V

2

2.5 V

0.3 V

100°F

167°F

5.0 V

3

2.5 V

0.3 V

100°F

113°F

5.0 V

4

4.0 V

0.1 V

68°F

185°F

5.0 V

5

4.0 V

0.1 V

68°F

167°F

5.0 V

6

4.0 V

0.1 V

68°F

131°F

5.0 V

7

4.0 V

0.1 V

68°F

189°F

5.0 V

8

4.0 V

0.1 V

68°F

189°F

5.0 V

9

4.0 V

0.1 V

68°F

163°F

5.0 V

10

4.0 V

0.1 V

68°F

127°F

5.0 V

11

4.0 V

0.1 V

68°F

194°F

5.0 V