2 bcm controller terminating resistor and bias, Gf-115-c, Modulex e8 controller and bcm – AERCO Modulex E8 Controls Guide User Manual

Page 69: Figure 7-9: bcm loop termination and bias

Advertising
background image

PR1: 11/30/12

Page

69 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

7.5.2 BCM Controller Terminating Resistor and Bias

BCMs can function only as Slave devices on a Modbus Network. Since the Slaves are

connected in a “Daisy-Chain” configuration, the terminating resistor must be enabled only in the

last BCM Controller in the chain. Enabling the terminating resistor is accomplished by

positioning jumper JP1 as shown in

Figure 7-9 only on the BCM Board contained in the last

BCM Controller.
As mentioned in

paragraph 7.5.1, when the controlling Master is an EMS or BAS, pull-down

bias may be implemented by connecting a 1K ohm resistor as shown in

Figure 7-9. DO NOT

install this bias resistor if the controlling Master is an AERCO BMS II or ACS. Bias will be

provided by the BMS II/ACS DIP switches. The last unit in the chain must be energized (even if

disabled) to enable bias.

Y2

Y3

Y4

Y1

SW1

A1

I

0

BCM FRONT VIEW

7 6 5 4 3 2 1

Y2

JP2

JP1

T

C
V

JUMPER

SHOWN IN

“TERMINATED”

POSITION

1K OHMS

PULL-DOWN

BIAS

RESISTOR

DO NOT

INSTALL BIAS

RESISTOR

WHEN BMS II

IS “MASTER”

Figure 7-9: BCM Loop Termination and Bias


Advertising