GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

NOTE

All DISPLAY Menu & Sub-Menu functions are READ ONLY and

cannot be changed. Temperature readings shown are in °F.

Table 4-1: DISPLAY Menu Listing

FUNCTION

DESCRIPTION

REMARKS

INSTALLATION Sub-Menu

T-OUTSIDE

Outside air temperature

Displayed only if outside

air sensor is installed.

T-EXT DES

Boiler Set Point setting in 0 to 10 volt input

mode

A 0 to 10 volt external

input signal can be used to

change the Boiler set

point.

T-COLL DES

Boiler Set Point temperature in Indoor/ Outdoor

Reset and Constant Set Point modes.

T-COLLECTOR Header Set Point temperature (cascade)

T-BOIL

Press Program Key to display temperature

and ON/OFF status of individual Heat

Modules (HS) which range from 2 (MLX-

303) to 7 (MLX-1060). Turn Rotary Knob to

sequence between Heat Modules.

The Burner symbol ( )

is displayed when the

respective Heat Module is

ON.

T-SOLID FUEL

Not Applicable

T-RETURN 1

Not Applicable

T-RETURN 2

Not Applicable

T-BUFFER T

Not Applicable

T-BUFFER M

Not Applicable

T-BUFFER L

Not Applicable

T-STORAGE 3

Not Applicable

MODGRAD

Press Prog Key to display Modulation % for

individual Heat Modules (HS). Turn Rotary

Knob to sequence between Heat Modules.

RETURN

Press Program Key to exit INSTALLATION

Sub-Menu.

HOT WATER Sub-Menu

T-DHW RATED DHW set point temperature

Based on heating prog and

operating mode. Actual

DHW set point as set in

USER/HOT WATER

menu.

T-DHW

Actual hot water temperature

Only if tank sensor is

installed

T-DHW L

Not Applicable

T-CIRCL

Not Applicable

RETURN

Press Program Key to exit the HOT

WATER Sub-Menu.