5.3.3 Setting the Voltage and Set Point Limits for U1/U2 and T1/T2

NOTE

Ensure that steps 1 through 13 in

Paragraph 5.3.2 were

completed prior to performing the following steps.

NOTE

When scrolling through sub-menus and functions, enter required

Code 0000 only when prompted to do so. Normally, Code 0000

only needs to be entered once, unless you exit and re-enter

EXPERT menu.

U1 and U2 settings: To set the voltage limits corresponding to the minimum and maximum

allowable set point limits, follow the instructions below.

Voltage & Set Point Limits: U1 & U2

1. Press the Program Key to enter the

EXPERT menu – INSTALLATION sub-menu. The

display will show

CODE NO. requesting the valid code to be entered.

2. Enter code

0000 (4 zeros) by pressing the Program Key four times. The red LED will

remain lit while the four code digits are entered. A dashed line will appear in the display

following code entry.

3. Next, turn the Rotary Knob clockwise until

CURVE 11-U1 is displayed.

4. Press the Program Key. The red LED will light.

5. Enter the desired low voltage limit for U1 by turning the Rotary Knob. The voltage will

increment in 0.10 volt increments.

6. With the desired low voltage limit displayed, press the Program Key to set the U1 voltage.

The red LED will go off.

7. Turn the Rotary Knob clockwise and scroll to

CURVE 11-U2.

8. Press the Program Key. The red LED will light.

9. Enter the desired high voltage limit for U2 by turning the Rotary Knob.

10. With the desired high voltage limit displayed, press the Program Key to set the U2 voltage.

The red LED will go off.