Table 9-4: BCM Standard Holding Register Address Mapping (Continued)

Modbus

Data

Address

Menu Item

Units and Range

Default/(Comments)

OPERATING DATA REGISTERS (Continued)

1020

Operating Mode

enum (0, 1, 2, 3, 6)

0: Standby

1: Space Heating

2: DHW

3: Check

6: Test

(Read Only)

1100

Linked BMM

Flags (0 -255)

Bit 0: BMM #0

to

Bit 7: BMM #7

(Read Only)

1101

Inserted BMM

Flags (0 -255)

Bit 0: BMM #0

to

Bit 7: BMM #7

(Read Only)

1102

BMM in Check Mode

Flags (0 -255)

Bit 0: BMM #0

to

Bit 7: BMM #7

(Read Only)

1103

BMM Flame Status

Flags (0 – 255)

Bit 0: BMM #0

to

Bit 7: BMM #7

(Read Only)

1104

BMM Alarm Status

Flags (0 – 255)

Bit 0: BMM #0

to

Bit 7: BMM #7

(Read Only)

1108

BMM Maximum Modulation Level 0 – 100% (Value x 10)

(Read Only)

1109

Pump Modulation Output

0 – 10V

(Read Only)

1200

Monitor Only

0 – 100%

(Read Only) Global modulation level

from Cascade Manager

2n00

BMM #n Error Code

(n = 0 – 7)

0 – 0xFFFF

(Read Only)

2n02

BMM #n Outlet Temperature

(n = 0 – 7)

14°F to 212°F (-10°C to

100°C) (Value x 10)

(Read Only)

2n08

BMM #n Actual Modulation

Level (n = 0 – 7)

0 – 100%

(Read Only)