4.7.1 CAP/MODULE Function (Maximum Kilowatts per Burner)

When the Program Key is pressed with CAP/MODULE displayed, the display may show

“SCAN”, indicating that the Controller is searching for related MODULE (BOILER) functions.

Once the scan is complete, follow instructions below.

CAP/MODULE Function (Setting Max. Kw per Burner)

1. Press the Program Key. The display will show CODE NO., requesting the valid code to be

entered.

2. Enter code

0000 (four zeros) by pressing the Program Key four times. The red LED will

remain lit while the four code digits are entered.

3. Press the Program Key
4. The display will show

BOILER 1 (meaning Heat Module 1), along with kilowatt (Kw) setting

for the first Module. The default setting for each Boiler Module is 40 Kw.

NOTE

The

40 Kw setting is only a control parameter. It does not

represent the maximum input of each module.

5. If the desired Kw setting is not displayed, press the Program Key and change the setting

using the Rotary Knob. Once the desired setting is displayed, press the Program Key to

store the value.

6. Continue scrolling through each

BOILER (Heat Module) and observe the Kw setting for

each one. Change as needed by repeating step 5.

7. Once all

BOILER modules have been set, RETURN will be displayed.

8. Press the Program Key to continue with the next menu function (

RELAY FUNC 1) in the

INSTALLATION Menu Table.