Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

NOTE

Whenever “

CODE NO.” is displayed, it indicates that the valid

password must be entered. This is accomplished by entering code

0000 (four zeros) by pressing the Program Key four (4) times.

Table 4-3: EXPERT Menu Listing

FUNCTION

DESCRIPTION

ENTRY RANGE

DEFAULT

INSTALLATION Sub-Menu

CODE-NO

Permits entry of valid Code No.(0000)

0000 - 9999

0000

BUS ID HS

BUS ID HS

MUST be set to - - - - to operate

the boiler

01 - 08

DO NOT

CHANGE

BUS ID 1

The heating circuits are sequentially

numbered starting with „01“, heating circuit

numbers must not be assigned twice.

(00), 01 – 15

01

BUS ID 2

Heating circuits are sequentially numbered

starting with “01“, heating circuit numbers must not

be assigned twice.

(00), 01 – 15

- - - -

AF SUPPLY

Outdoor sensor power supply

00, 01 (OFF/ON)

01 (ON)

BUS TERM

Bus terminating resistor (Must be set to 01)

00, 01 (OFF/ON)

01 (ON)

EBUS

SUPPLY

Switches the Ebus supply ON/OFF

00, 01 (OFF/ON)

01 (ON)

TIME

MASTER

Not Applicable

MAX T-COLL

Sets the maximum allowable header set

point temperature.

86.0°F – 230.0°F

185.0°F

MIN T-COLL

Sets the minimum allowable header set point

temperature.

50.0°F – 176.0°F

50.0°F

MAX T-HS2

Not Applicable

MIN T-HS2

Not Applicable

V-CURVE

0 to 10 Volt input Voltage curves. Choose

from preset curves (see para. 3.5.1) or

customize a curve.

00 – 11

11

CURVE 11-U1

Low voltage setting

0.00V – 10.00V

0.000

CURVE 11-U2

High voltage setting

0.00V – 10.00V

10.00

CURVE 11-T1

Minimum set point temperature

32.0°F – 248.0°F

59.0°F

CURVE 11-T2

Maximum set point temperature

32.0°F – 248.0°F

185.0°F

CURVE 11-UO

Stop/Start voltage level. Going below/above

this setting will stop/start the Boiler.

0.00V – 10.00V

1.00