Gf-115-c, Modulex e8 controller and bcm, Fi gur e 7- 11 – AERCO Modulex E8 Controls Guide User Manual

Page 72: Operations and maintenance manual

Advertising
background image

PR1: 11/30/12

Page

72 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

Figure

7-

11

.

EMS

/BAS Master Controlling Modulex Boiler Slaves

TO OTHER NETWORK BOILER SLAVES

(3

- 9

)

(SEE NOTE

3)

EMS MASTER

T+/

R

+

T-

/R

-

RS485

PORT

SHIELD

+

Y

2-

2

– MODBUS “A”

(-

)

(PART OF BCM CONN

. Y

2)

MODULEX BOILER SLAVE

#1

NOTES

:

1.

IF EMS MASTER CONTAINS A

4-

WIRE RS

485

PORT

,

TIE THE TWO POSITIVE

(+)

AND NEGATIVE

(-

)

LEADS TOGETHER AS SHOWN IN DETAIL “A”

2.

IF EMS MASTER CONTAINS ONLY A RS

232

PORT

, A RS

232

-TO

-RS

485

CONVERTER WILL BE

REQUIRED

.

3.

THE LAST BCM SLAVE ON THE RS

485

LOOP

MUST HAVE ITS TERMINATION RESISTOR ENABLED

.

ALSO

,

A

1K OHM BIAS RESISTOR

MAY BE REQUIRED

.

CHECK WITH THE EMS

MANUFACTURER

.

SEE NOTES

1

&

2

DETAIL “A” (SEE NOTE

1)

T+

T-

4-WIRE RS

485 PORT

SHIELD

R

+

R

-

T+/

R

+

T-

/R

-

Y

2-

1

– MODBUS “B”

(+)

BCM

+

Y

2-

2

– MODBUS “A”

(-

)

(PART OF BCM CONN

. Y

2)

MODULEX BOILER SLAVE

#2

Y

2-

1

– MODBUS “B”

(+)

BCM

Fi

gur

e

7-

11

: