1 operating scenario, Gf-115-c, Modulex e8 controller and bcm – AERCO Modulex E8 Controls Guide User Manual

Page 65

Advertising
background image

PR1: 11/30/12

Page

65 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

Y2

Y3

Y4

Y1

SW1

A1

I

0

7 6 5 4 3 2 1

Y2

SEE CHART

RESISTOR

SETPOINT

160°F

120°F

100°F

140°F

100K OHMS

47K OHMS

22K OHMS

10K OHMS

180°F

OPEN

SHORT

80°F

Figure 7-5: Installing Resistor to Change Default Setpoint

7.4 BCM Configured as Primary Controller Utilizing Modbus

NOTE: When the BCM is configured as the primary controller, the E8 will display the

fault code “E200”.

The BCM can be configured as the Primary Controller, instead of the E8, when it is connected

to a Modbus Network. However, the E8 must be disconnected from the e-Bus connection on

the BCM Board (see

Paragraph 7.4.3). All Modbus Networks are implemented utilizing a

“Master – Slave” scenario where only one device, the “Master”, can initiate a communication

sequence. However, BCMs can only function as “Slave” devices on a Modbus Network.

Therefore, the BCM must be interfaced to an external controlling “Master”. The “Master” can be

AERCO’s Boiler Management System II (BMS II), AERCO Control System (ACS), or an Energy

Management System (EMS)/Building Automation System (BAS) developed by other

manufacturers.
The following subordinate paragraphs provide descriptions of Modbus Network operation and

required wiring connections between the BCM “Slaves and the controlling “Master” (EMS, BAS).
Detailed information on the Modbus Function Codes, Input/Holding Register Assignments and

other Modbus requirements supported by the BCM are provided in

Section 9 of this document.

7.4.1 Operating Scenario

Each Modulex Boiler must be equipped with its own BCM to allow Modbus Network monitoring

and control. An EMS or BAS Master can control the Networked Modulex Boilers utilizing

Remote Setpoint. An AERCO BMS II Master can control the networked Modulex boilers utilizing

a Modbus signal.