7.4.3 Disconnecting the E8 from the E-Bus on the BCM Board.

NOTE

When the BCM is configured as the primary controller, the E8 will

display the fault code “E200”.

If the BCM was retrofitted in the field utilizing

Technical Service Bulletin 2007-07, refer to this

bulletin and disconnect CBL 24 from Connector VII on the E8 Controller. However, if the

Modulex Boiler was shipped with the BCM factory-installed, it will contain a 3-position switch

mounted above the BCM (

Figure 7-8). Refer to the switch matrix in Table 7-1 for descriptions of

how the factory-installed 3-position switch functions with respect to the 2-position ON/OFF

(Enable/Disable) switch on the BCM.

Table 7-1: 3-Position BCM Switch Functions

BCM 2-Pos Switch

(Enable/Disable)

BCM 3-Pos Switch

(Equivalent Terminal in Modulex Wiring Diagram)

Position I

(1b)

(NOTE 1)

Position O (0)

(see NOTE 2)

Position II (1a)

(See NOTE 3)

O (OFF)

(Disable)

DO NOT

USE

The BCM is the Gate-way

for Modbus and external

control. The E8 does

not

control the boiler and the

BCM will

not take over the

boiler if the Modbus signal

fails.

The E8

is the primary

controller and the BCM

allows monitoring

through Modbus, but

will

not take over boiler if the

E8 fails.

I (ON)

(Enable)

DO NOT

USE

The BCM is the Gate-way

for Modbus and external

control. The E8 does

not

control the boiler and the

BCM

will take over the

boiler if the Modbus signal

fails. If E8 is in Standby

Mode, BCM will cycle the

pump with the boiler. If E8

is in Day Mode, the E8 will

continuously run the pump.

The E8

is the primary

controller and the BCM

allows monitoring, and

the BCM

will take over

the boiler if E8 fails. If E8

is in Standby Mode, E8

will cycle the pump (must

use Enable/Disable). If

E8 is in Day Mode, the

E8 will continuously run

the pump.

NOTES:

1.

DO NOT set the 3-Position Switch to Position I.

2. Set the 3-Position Switch to Position

O ONLY when controlling Boilers from an external

Controller via Modbus Communication. See

Paragraph 3.1.2 for setting HEAT Modes.

3. Position

II is the Default position for the 3-Position Switch. Ensure it is set to this position

when it arrives from the Factory. See

Paragraph 3.1.2 for setting HEAT Modes.