GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

5.1.3 Viewing the Boiler Setpoint

The setpoint temperature setting is viewed in the E8 controller display as shown below.

Viewing the Boiler Setpoint

1. Turn the Rotary Knob to the

DISPLAY menu. The first sub-menu displayed will be

INSTALLATION.

2. Press the Program Key to enter the

INSTALLATION sub-menu.

3. Turn Rotary Knob clockwise until

T-COLL DES is displayed along with corresponding

temperature reading. This

T-COLL DES reading equals the boiler set point.

5.2 Constant Set Point Mode

When a fixed header temperature is desired, configure the the Constant Set Point Mode as

shown in the instructions below.

Constant Setpoint Mode Configuration

1. Set the ON/OFF switch on the front of the Modulex boiler to the ON position.
2. Open the Controller front panel.
3. Turn the Rotary Knob clockwise to the

EXPERT menu. The first item (sub-menu) displayed

will be

INSTALLATION.

4. Continue turning the Rotary Knob clockwise until

HEAT CIRCUIT 1 is displayed.

5. Press the Program Key to enter the

HEAT CIRCUIT 1 sub-menu.

6. Scroll to

HC FUNCTION. The currently stored setting (00 or 01) will be displayed. Normally,

00 will be displayed since this is the Factory Default. However, for the Constant Set Point

Mode, the

HC FUNCTION setting must be changed to 01. If the HC FUNCTION is currently

set to 00, proceed to step 7. However, if it is set to 01, skip to step 11.

7. If the

HC FUNCTION is set to 00, press the Program Key. CODE NO. will be displayed

requesting the valid code to be entered.

8. Enter code

0000 (four zeros) by pressing the Program Key four times. The red LED will

remain lit while the digits are entered.

9. With

HC FUNCTION again displayed, press the Program Key. The red LED will light. Turn

the Rotary Knob to change the

HC FUNCTION to 01.

10. Press the Program Key to store the 01 setting for the

HC FUNCTION. Red LED will go off.

RESET will be momentarily displayed, followed by display of the current Controller software

version (e.g. SW 259-04). Following

RESET, the Controller display will then switch to the

initial

INSTALLATION menu.

11. Use Rotary Knob to scroll to the

USER menu and access HTG CIRCUIT 1 sub-menu. Press

Program Key to enter the sub-menu.

12. Using Rotary Knob, scroll to

T – FLOW DAY. The currently stored value for T – FLOW DAY

will be displayed. This represents the current Constant Set Point temperature in °F.

13. To change Constant Set Point value, press the Program Key and turn the Rotary Knob to

select the desired Constant Set Point. Press the Program Key again to store the Set Point.