Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

Table 4-3: EXPERT Menu Listing (Continued)

FUNCTION

DESCRIPTION

ENTRY

RANGE

DEFAULT

HEAT CIRCUIT 1 & 2 Sub-Menus

The Sub-Menu Functions for HEAT CIRCUIT 1 & HEAT CIRCUIT 2 are identical, except for

the MIXER OPEN & MIXER CLOSE Functions which apply only to HEAT CIRCUIT 1. The

Function values in this Sub-Menu level will change, depending on the Heat Circuit Function

(HC FUNCTION) selected.

HC FUNCTION

Heat Circuit Function defines type of

circuit:

00 = Standard Heat Circuit

01 = Control to fixed flow temperature

02 = Swimming pool control (HC 2

ONLY)

03 = Hot Water Circuit

04 = Return flow temp. Increase via

mixing valve.

00 – 04

00

(Standard

Heat

Circuit)

PUMP MODE

Circulation pump mode control for

ON/OFF switching of pumps.

00 = Standard pump control

01 = Pump switching per heating limits

02 = Pump switching per heating program

03 = Continuous pump operation

00 – 03

00

MIXER OPEN

Not Applicable

MIXER CLOSE

Not Applicable

MAX T-FLOW

Maximum allowable water temperature

setting for the heating circuit.

68°F – 230°F

176°F

MIN T-FLOW

Minimum allowable water temperature

setting for the heat circuit.

50°F – 230°F

50°F

T-FROST PROT

Specifies the minimum allowable outside

air temperature setting for the Frost

Protection Mode. If temperature drops

below this value, the system switches to

the Frost Protect Mode and the pumps

are switched ON.

(This Function should be set to 0°F in the

INSTALLATION Mode)

-5°F – 41°F

32°F

OUT-TEMP-

DEL

Not Applicable

N/A

N/A

SLOPE

OFFSET

Not Applicable

N/A

N/A

B-HEAT SINK

Not Applicable

N/A

N/A

RETURN

Press Program Key to exit HEAT

CIRCUIT 1 (or 2) Sub-Menu.