5.4.4 Displaying Temperatures Associated With DHW

Functions in the

DISPLAY menu are used to display the actual DHW temperature measured by

the tank sensor. The swing-down hinged panel must be open to access and display these

functions.

5.4.4.1 Viewing DHW Set Point and Actual DHW Temperature

The DHW set point and the actual DHW temperature measured by the tank sensor are

displayed as shown in the instructions below.

Viewing DHW Setpoint and Actual DHW Temperature

1. Turn the Rotary Knob to the

DISPLAY menu. The first sub-menu displayed will be

INSTALLATION.

2. Continue turning the Rotary Knob clockwise until the

HOT WATER sub-menu is displayed.

3. Press the Program Key to enter the

HOT WATER sub-menu.

4. Turn Rotary Knob to display

T-DHW RATED. The temperature value shown is the DHW

set point temperature.

5. Next, scroll to

T-DHW. The temperature value shown is the actual DHW temperature

measured by the tank sensor.

6. Continue scrolling until RETURN is displayed. Press the Program Key to exit the

HOT

WATER sub-menu.

5.4.4.2 Viewing DHW Set Point With T-BOILER DHW Function

The setting for T-BOILER DHW, in the EXPERT/HOT WATER Menu, adds to the Domestic Hot

Water setpoint (T-DHW RATED), becoming the final supply water temperature to the domestic

hot water tank. The T-COLL DES reading equals the DHW setpoint plus the value of the T-

BOILER DHW function or T-DHW RATED + T-BOILER DHW = T-COLL DES.

EXAMPLE: If T-DHW RATED is set at 140° and T-BOILER DHW is set at 45°,

then the T-COLL DES (Boiler Outlet Temperature) will be 185°.

To view DHW set point with the T-BOILER DHW setting already added to it, refer to the

instruction below.

Viewing DHW Setpoint with T-BOILER DHW Function

1. Turn the Rotary Knob to the

DISPLAY menu. The first sub-menu displayed will be

INSTALLATION.

2. Press the Program Key to enter the

INSTALLATION sub-menu.

3. Turn the Rotary Knob clockwise until

T-COLL DES is displayed along with corresponding

temperature reading.