Gf-115-c, Modulex e8 controller and bcm – AERCO Modulex E8 Controls Guide User Manual

Page 52

Advertising
background image

PR1: 11/30/12

Page

52 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

5.4.2 Configuring the Controller for DHW With a Tank Sensor

Both EXPERT and USER Menus will be used to configure the Controller for DHW production.

The DISPLAY Menu will be used to display the set point. Follow instructions below to configure

the controller for DHW with a tank sensor.

IMPORTANT

The tank sensor MUST be connected (

Section 5.4.1), prior to

configuring Controller for DHW operation. If sensor is not

connected, many required functions will not display.

Configure the Controller for DHW with a Tank Sensor

1. With Controller front cover

closed, turn Rotary Knob until Faucet symbol (

) appears in

the lower part of the of the display window.

2. Next, open Controller front panel.

3. Turn Rotary Knob clockwise to

EXPERT, HOT WATER sub-menu.

4. With

HOT WATER displayed, press the Program Key to enter sub-menu.

5. Scroll through

HOT WATER sub-menu turning Rotary Knob clockwise until THERM INPUT

is displayed with the current setting (00 or 01). If 00 is displayed (sensor), skip to step 6.

6. If the

THERM INPUT is currently set to 01 (Aquastat), press Program Key to change the

THERM INPUT. The display will show “CODE NO.”, requesting entry of a valid code.

7. Enter code

0000 (four zeros) by pressing the Program Key four times. The red LED will

remain lit while the four code digits are entered.

8. With

THERM INPUT again displayed and the red LED lit, turn Rotary Knob to change to 00

for sensor operation.

9. Press Program Key to store 00 setting for

THERM INPUT. Red LED is off.










Advertising