PR1: 11/30/12

Page

28 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

Table 4-3: EXPERT Menu Listing (Continued)

FUNCTION

DESCRIPTION

ENTRY RANGE

DEFAULT

INSTALLATION Sub-Menu (Continued)

HYSTERESIS

Not Applicable

FOUND

MODULS

Displays the number of heat modules available

for service.

Display

CAP/MODULE

Displays the maximum Kw output of each heat

module.

00 – 1000 Kw

40 Kw

NEW CONFIG

Not Applicable

MIN MOD

CASC

Not Applicable

01 – 08

01

HW-BOILER

Not Applicable

00 – 08

00

CONTR

DEVIAT

Control Deviation indicates the temperature

difference between the Boiler set point and the

actual water temperature.

Display

°F

DES OUPUT

Required system output [in %]

0 – 100%

00

SWITCH TIME

Not Applicable

(N/A)––

(N/A)

BLOCK TIME

Not Applicable

(N/A)

(N/A)

MAX T-

MODUL

Maximum temperature of Heat Module

122.0°F to 230.0°F

194.0°F

DYN

UPWARD

Not Applicable

(N/A)

(N/A)

DYN

DOWNWARD

Not Applicable

(N/A)

(N/A)

RESET TIME

Not Applicable

5 – 500

50

MODULAT

MAX

Start Level. If this modulation percentage is

exceeded, the next heat module is connected

after the delay time elapses.

50% - 100%

30%

MODULAT

MIN

Stop Level. If value drops below this

modulation percentage, the last heat generator

(module) of the current sequence is switched

off

10% - 60%

35%

MIN MOD HS

Not Applicable

0% - 60%

35%

MOD LEVEL

HW

Not Applicable

SEQUENCE 1

Boiler sequence 1

12345678

SEQUENCE 2

Boiler sequence 2

87654321