Table 10-4: BMM Fault Codes (Continued)

CODE DESCRIPTION

EFFECT

CORRECTION

RESET

24

Fan speed out of

control: It

doesn't reach

pre-purge speed

within 30

seconds.

Ignition retry

after 60

second delay

and failure

remains until

we have a

successful

burner

operation.

Check fan wiring.

AUTOMATIC/MANUAL

26

Fan speed out of

control: It

doesn't stop

within 30

seconds after

turned OFF.

Ignition is

inhibited.

Check fan wiring.

AUTOMATIC

27

Air flow failure

during ignition.

Restart pre-

purge timer.

The failure

remains until

we have a

successful

burner

operation.

Check fan and wiring.

Check air proving switch

and wiring.

AUTOMATIC

30

Settings

Corrupted

Ignition is

inhibited.

Pump runs for

5 min at max

speed.

Re-program the settings.

Contact Factory

MANUAL - cycle the

power or send reset

message.

32

Line voltage too

low. (<96 VAC)

Wait for

proper line

voltage. (>102

VAC)

Check input voltage else

try another BMM.

AUTOMATIC

40

Low Water Flow.

Low water flow

switch activated.

Burners

turned OFF.

Check water flow or

check switch.

AUTOMATIC