Table 8-4: EXPERT Menu Sub-Menus and Parameters (Continued)

FUNCTION

DESCRIPTION

ENTRY RANGE

DEFAULT

HEAT CIRCUIT 1 & 2 Sub-Menus

The Sub-Menu Functions for HEAT CIRCUIT

1 & HEAT CIRCUIT 2 are identical. The

Function values in this Sub-Menu level will

change, depending on the Heat Circuit

Function (HC FUNCTION) selected.

HC FUNCTION

Heat Circuit Function defines type of circuit:
00 = Standard Heat Circuit
01 = Control to fixed flow temperature
02 = Swimming pool control (HC 2 ONLY)
03 = Hot Water Circuit
04 = Return flow temp. increase via mixing

valve.

00 – 04

00

(Standard

Heat

Circuit)

PUMP MODE

Circulation pump mode control for ON/OFF

switching of pumps.

00 = Standard pump control
01 = Pump switching per heating limits
02 = Pump switching per heating program
03 = Continuous pump operation

00 - 03

00

MIXER OPEN
(NOT for HW

circuit)

Specifies speed setting at which mixer motor

opens when there is a control temperature

difference.Entering small temperature

difference values may cause the mixing valve

to oscillate

5°F -25°F

18°F

MIXER CLOSE
(NOT for HW

circuit)

Specifies speed setting at which mixing valve

closes when there is a control temperature

difference.

Entering small temperature difference values

may cause the mixing valve to oscillate

5°F -25°F

12°F

MAX T-FLOW

Maximum allowable water temperature setting

for the heating circuit.

68°F – 230°F

176°F

MIN T-FLOW

Minimum allowable water temperature setting

for the heat circuit.

50°F – 230°F

50°F

FROST PROT

Specifies the minimum allowable outside air

temperature setting for the Frost Protection

Mode. If temperature drops below this value,

the system switches to the Frost Protect

Mode and the pumps are switched ON.

-5°F – 41°F

32°F

OUT-TEMP-DEL

Outside Temperature Delay. Specifies the

elapsed time before a decrease in the outside

temperature will affect the indoor room

temperature. The time entered must be

consistent with the type of building

construction (i.e., thick well-insulated walls

can use a long time delay. For light, poorly

insulated structures, set time to 0 hours)

0:00 – 24:00

0:0

(N/A)

SLOPE OFFSET

Heating slope distance.

32°F – 194°F

48°F

(N/A)