1. System Configuration

1.8

List of I/O Modules

This manual explains the basic I/O modules in the list below and

how to use them.

Type

Specification

DI334

DC

input

32 points (8 pts common), 12 to 24 Vdc,

10 mA/point

DI334H

32 points (8 pts common), 12 to 24 Vdc,

10 mA/point, high-speed response

D1335

64 points (8 pts common), 24 Vdc,

5 mA/point

DI335H

64 points (8 pts common), 24 Vdc,

5 mA/point, high-speed response

IN354

AC

input

32 points (8 pts common), 100 to 120 Vac,

10 mA/point

IN364

32 points (8 pts common), 200 to 240 Vac,

10 mA/point

D0333

DC

output

16 points (8 pts common), 12 to 24 Vdc,

2 A/point, 5 A/common

D0334

32 points (16 pts common), 12 to 24 Vac,

0.5 A/point, 5 A/common

D0335

64 points (8 pts common), 5 to 24 Vdc,

100 mA/point

AC363

AC

output

16 points (8 pts common), 100 to 240 Vac,

2 Appoint, 5 A/common

AC364

32 points (16 pts common), 100 to 240 Vac,
0.5 A/point, 3.2 A/common, 5 A/module

R0364

Relay

output

32 points (8 pts common), 240 Vac/24 Vdc,
2 A/point, 5 A/common

R0363S

16 points (isolated contact), 240 Vac/24 Vdc,

2 A/point

For details on the specification of I/O modules, see 2.3, I/O

module specifications.

Carefully read the Cautions described In Section 3 for applying

I/O modules.

The I/O module can be mounted in any I/O slot functionally.

However, to improve noise-immunity for the entire system, it is

recommended to separate the low voltage 1/Os and the power

I/Os. (See 4.7, I/O Wiring.)