I/o module specifications, Point dc input, 3 i/o module specifications – Toshiba Programmable Controller PROSEC T3 User Manual

Page 36: Specification, 3 i/o module specifications 32-point dc input

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

2. Specification

2.3

I/O module

specifications

32-point DC input

Type

Category

input type

Number of input points

insulating method

Rated input voltage

Range of input voltage

Rated input current

Input impedance

Opera­

tion
voltage

Delay

Min. ON voltage

Max. OFF voltage

OFF-ON

ON — OFF

Input signal display

External connection

No. of commons

No. of input points
per common

Polarity of common

Derating condition

Internal cunent

consumption

Insulation resistance

Withstand voltage

Weight

Internal circuit

DI334

DI334H

DC input

Current sinking/sourdng

32 points. 2-word input (X 2 W)

Photo-coupler

12to24Vdc

10 to 26.4 Vdc

10 mA (at 24 Vdc)

2.4 KQ (at 24 Vdc)

9.6V

3.5V

10 ms or less

15 ms or less

1 ms or less

1.5 ms or less

LED display for all points, lit at ON, internal logic side

38-pin removable tenninal block, M3.5

4 (insulated between commons)

8 points/common

No Polarity

See NOTE on the next pate

5 Vdc, 100 mA or less

10 MQ or more (500 Vdc)

1500 Vac, 1 minute (between commons, between

internal and external circuits)

420g

28

PROSEC T3