6. Troubleshooting

6.3

Checking the CPU

6.4

Checking program

If the POWER LED is lit, but the RUN LED is not lit, check the

following points:

Change to RUN or P-RUN.

If the switch is in RAM, the CPU

does not enter into the RUN mode

automatically. (Stand-by mode)

The blinking RUN LED indicates In

the HOLD mode. Check that the

HOLD device (S0401) is not used in

the program.

An error-down has occurred.

Check the error by following the

procedure in Section 6.9.

Check the program based on the following points if it is running but

the operation does not work as intended.

(1) Output is not carried on the same coil or register of two or more

locations during one scanning: the devices for coil instructions
and for function instructions are not overlapping.

(2) The signal which changes faster than the scanning cycle is not

Input.

(3) Timer register or counter register is not duplicated.
(4) When an interrupt is used, the device/register which is used in

the main program is not operated erroneously in the interrupt

routine.

User's manual - Hardware

77