Error message and related information

Relevant

LED displays

Meaning of the error and

countermeasures

Error message

information

1

Information

2

information

3

special

relay

RUN

FAULT

I/O

Program

No sub-r entry

Program

type-

Block No.

Address

in the

block

Subroutine
No.

S0006
S0030

O

O

The "SUBR" instruction of the subroutine

No. specified by the "CALL" instruction is
not programmed. Insert the "SUBR"
instruction.

No RET error

Program

type-

Biock No.

Address
in the
biock

Subroutine
No.

S0006
S0030

o

0

The "RET" instruction is not programmed

in the subroutine.
Insert the “RET" instruction.

Sub-r nesting err

Program

type-
Btock No.

Address

in the

biock

Subroutine
No.

S0006
S0030

O

o

The number of nesting of subroutines

exceeds six overlays.

Change the program to reduce the number
of nesting overlays to six or fev^rer.

Loop nesting error

Program

type-

Block No.

Address
In the
block

S0006
S0030

o

0

The number of nestings of "FOR" and

"NEXT" instructions exceed six overlays.

Reduce the number of overlays of the

"FOR" and "NEXF instructions to six or

fewer in the program.

SFC step No. error

Program

type-

Block No.

Step No.

S0006
S0030

o

o

Step No. is duplicated in the SFC program,

or the step Nos. specified by the initial step
and the end step are not identical. Change
the step No., or check the step No. of the
end step.

SFC macro No. err

Program

type-

Biock No.

Macro No.

S0006
S0030

o

o

Macro No. is duplicated, or the same
macro program is called from two or more
locations.
Change the macro No. Or, limit the catling

of the macro program to one location.