4. Installation and Wiring

(4) Refer to the following table for the size of I/O cables.

Type of module

Cable size

16-point module

0.75~1.25 mm2

32-point module

0.5-0.75 mm2

64-point module

0.1 —0.3 mm2

Use a larger size cable for the common line. For the field-wiring

cable,

\

.25 mm^ or larger cable is recommended.

(5) The M3.5 screw is used as a terminal screw. Use an

appropriate crimp-type terminal with a width of 7 mm (0.28 in) or

less for the M3.5 screw.

(6) Do not bind the I/O signal cables and high-voltage or power

cables. Separate them as far as possible. If separation is

difficult, use shielded cables for the I/O signals and ground the

shield at the leading-in point of the control panel.

68