Part

Error message and related information

Relevant

special

relay

LED displays

Meaning of the error and

countermeasures

Error message

Information

1

Information

2

Information

3

RUN

FAULT

I/O

CPU

Clock-calendar err

SOOOA

An abnormality has been detected in the
data of the built-in calendar LSI
(No error-down occurs). If the abnormality
remains after the calendar is reset, replace
the CPU.

Illegal sys Intrpt

Interrupted '

address 1

Interrupted

address 2

The CPU module received a request for
interrupt not registered
(No error-down occurs).
If the abnormality occurs frequently,
replace the CPU module.

WD timer error

Address 1

Address 2

S0004
S001F

o

o

A watchdog timer error has been detected.
If the abnormality occurs frequently,
replace the CPU module.

I/O

I/O bus error

Unit No.

Data

S0005
S0020

o

An abnormality has been detected in I/O
bus checking. Check that the connection
of cables and the mounting conditions of
the modules are correct.

1/0 mismatch

Unit No. -

Slot No.

Register

No.

S0005
S0021

o

The I/O allocation information and the
actual I/O module mounting are not
identical. Set the I/O allocation information
correctly.

I/O no answer

Unit No. -
Slot No.

Register

No.

S0005

S0022

o

I/O modules are not mounted in the slots

where I/O allocation is specified. Mount

modules in the slots, or activate the system
in the RUN-F mode (forcible operation).

I/O parity error

Unit No. -
Slot No.

Register
No.

S0005
S0023

o

A parity error has been detected when

transferring data from/to I/O modules.
Check the mounting condition of the I/O
modules.