Toshiba Programmable Controller PROSEC T3 User Manual

Page 92

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

“0

X

О

со

m

о

00

Part

Error message and related information

Relevant

LED displays

Meaning of the error and

countermeasures

Error message

Information

1

Information

2

Information

3

special

relay

RUN

FAULT

I/O

Power

supply

System power on

Power ON (no error)

System power off

Power OFF (no error)

Expansion unit err'

S0005
S0024

О

The 5-volt power of the expansion unit, or
the termination of the expansion IF module

is not normai.

Check whether power suppiy to the
expansion unit is oveiioad; the power
suppiy of the basic unit Is ON but the
power supply of the expansion unit is
OFF; and the expansion IF module is

terminated correctly.

Power Interrupt

S001D

о

о

A power interruption is detected.

When the power interruption detecting

function is used, the operation is stopped

if a power interruption longer than the

specified time is detected.

Power intr resumed

S001C

The power interruption has been

recovered.

When the hot restart function is used, the

operation is restarted without initialization,

Memory

RAM check error

Address of
the error
occurred

Error data

Test data

S0004
S0012

о

О

An abnormality has been found in
executing rea^write check on the user
data memory (RAM),

if the abnormality continues after the

power supply is turned ON again, replace

the CPU module.

Program BCC error

BCC

error data

S0006
S0030

о

О

BCC check of the user program

memory (RAM) has detected an
abnormality. After "clear memory" is
executed, reload the program.

Batt voltage drop

SOOOF

■ ■“

When turning the power ON, the voltage
drop of the battery to back up the RAM
memory has been detected. (The ВАТТ

LED is off. No error-down.) Replace the

battery with a new one.

о>

О

с
2

ф

0)

о

о

нн

5’

(Q