4. Installation and Wiring

4.7

I/O wiring

The following module layout is recommended for noise immunity.

Duct for

low-voltage

signals

Duct for

power signals

Power

caUes

I/O modules for

low-voltage system

I/O modules for

power system

DC input module

AC input module

Analog input module

DC output module

Analog ou^ut module

AC output module

Pulse input module

Relay output module

ASCII module

Data link module

(1) To improve the unit's resistance to signal interference, install

modules for low-voltage signals toward the left of the unit, and

modules for power signals toward the right. Also, separate the

wires of each,

(2> Allow at least

too

mm (4 in) clearance between the units and

between other control equipment to allow access for

maintenance and ventilation,

(3) When installing the unit near high-voltage or high-power

equipment, leave at least 200 mm (8 in) clearance, or shield the

unit with a steel plate.

User's manual - Hardware