Part

Error message and related Information

Relevant

LED displays

Meaning of the error and

countermeasures

Error message

Information

1

Information

2

Information

3

special

relay

RUN

FAULT

I/o

I/O

Invalid I/O intrpt

Unit No. -
Slot No.

S0005
S0025

A request for I/O interrupt from an interrupt
module not registered has been detected
(No error-down occurs).
Register the interrupt module, or do not
mount that interrupt module.

Duplicate I/O reg

Unit No. -

Slot No.

Register

No.

S0005

S0021

O

An overlap is detected in allocating I/O
registers to I/O modules. Correct the I/O
allocation Information.

Illegal I/O reg

Unit No. -
Slot No.

Register
No.

S0005
S0021

o

The allocation of I/O modules to I/O
registers has exceeded the limit. Reduce
the number of allocations to I/O modules.

Proc­

essing

LP function error

Error code

Error data

S0004
S0015

o

o

An abnormality is detected in the language
processor (LP).
If the abnormality remains after power
cycle, replace the CPU module.

LP reg FVW error

Port No.

Error data

Test data

S0004
S0015

o

o

At initial setting of the language processor
(LP), an abnormality has occurred in the
read/write checking. If the abnormality
remains after power cycle, replace the
CPU module.

LP exec timeout

S0004

S0015

o

o

The execution of the language processor

(LP) did not finish within a time specified.
Reduce the program execution time or use

the "WOr instruction.

If the situation is repeated after power

cycle, replace the CPU module.

Scan time over

Scan time

S0006

S0031

o

O

The scan time exceeded 200 ms.

Reduce the scan time or use the "WDT"
instruction.

O)

H

o

c

2

(D

(n
D"

O
O

(O

Advertising