The table below lists the internal 5 Vdc current consumption (max.)

of the module for calculating allowable power capacity.

Type

Name

Part No.

Internal 5-

volt current

ccxisumption

Expansion

interface

Standard expansion interface
(for basic unit)

IF311

20 mA

Standard expansion interface
(for expansion unit)

IF351

20 mA

Long-distance expansion interface
(for basic unit)

IF312

800 mA

Long-distance expansion interface
(for middle expansion unit)

IF352

700 mA

Long-distance expansion interface
(for end expansion unit)

IF353

700 mA

CPU

CPU (RAM)

PU315

2.5 A

CPU (EEPROM+RAM)

PU325

2.5 A

DC

input

32-point DC input

DI334

100 mA

32-point DC input
(high-speed response)

DI334H

100 mA

64-point DC input

DI335

170 mA

64-point DC input
(high-speed response)

DI335H

170 mA

AC

input

32-point AC input (100 to 120 Vac)

IN354

120 mA

32-point AC input (200 to 240 Vac)

IN364

120 mA

DC

output

16-point DC ou^ut (12 to 24 Vdc)

D0333

320 mA

32-point DC output (12 to 24 Vdc)

D0334

210 mA

64-point DC output (5 to 24 Vdc)

D0335

400 mA

AC

output

16-point AC output (100 to 240 Vac)

AC363

530 mA

32-point AC ou^ut (100 to 240 Vac)

AC364

800 mA

Relay

output

32-point relay output

R0364

170 mA

10-point relay output (Isolated)

R0363S

100 mA

Special

I/O

Analog Input (8 channels)

AD368

460 mA

Analog output
(4 channels)

Voltage

DA364

180 mA

Current

DA374

180 mA

Pulse input (2 channels)

P1312

800 mA

DC input (8 pts) with status change

detection

CD332

300 mA

ASCII interface

AS311

1 A

Data link

TOSL1NE-S20

Coaxial

SN321

800 mA

Optic

SN322

800 mA

Coaxial/optic

SN323

800 mA

TOSLINE-F10 (master)

MS311

1 A

Note) The current consumption of the T3 CPU modules (2.5 A max.) is

the value when the handy programmer (HP911) is connected.