4. Installation and Wiring

4.5

Grounding

Check points for

grounding

Grounding of

controi panei

To maintain the safety and stable operation of the T3, grounding is
very important. Read and follow the check points below before
grounding.

Check the grounding against the following criteria:

(1) The T3 must not become a path for ground current. High-

frequency current is particularly harmful.

(2) Equalize the ground potentials of the basic and the

expansion units. Ground them at a single point.

(3) Do not connect the ground of the T3 to that of high-power

systems.

(4) Do not use a ground that has an unstable impedance, such

as painted screws, or grounds subject to vibration.

In some cases, the T3 unit becomes a path of ground current from a

power panel or high-frequency equipments.

^Change

Isolate the T3 mounting

panel and connect to the

ground point separately.

Isolate the T3 from the

mounting frame and connect

to the ground point separately.