1. System Configuration

For example, if the user is going to mount a power supply module

on the expansion unit No.2, check that the following conditions are
satisfied.

Conditions for the power supply
capacity of the basic unit

Conditions for the power supply

capacity of expansion unit No.2

Additional power supply modules may be mounted on the units

even though the power supply capacity has enough margin.

(1) lo+li<7A
(2) 5.1-RoXh > 4.75V

(3)

l2+l3

< 7A

(4) 5.1-R2Xl3>4.75V

NOTE (1) Correctly set the power supply mode plug of the

\~ZiX7 expansion interface module (IF351) according to a

power supply module to be mounted on the unit. If

the setting is wrong, the T3 will not work normally.

(For details, see 1.6 Expansion interface module.)

(2) For the long-distance expansion interface module,

each of the units must be equipped with a power

supply module.

The table below shows the resistance values (typical value) of

expansion cables.

Cable

length

Part No.

Resistance

value

0.5m

CS3R5

38m Q

1m

CS301

66m Q

2m

CS302

112mQ

Remarks

Standard type

With both-end connectors

(50-pin)

24

PROSEC T3