3. Precautions for I/O Modules

(5) Because the input filter time constant of the high-speed

response input module (DI334H, D1335H) is set to small, the

input module may read the wrong input due to chattering of the
contact. Use the high-speed response input module to connect

with solid-state devices. Also, take measures to suppress noise.

(6) If input wiring is too long, take measures to prevent erroneous

input caused by noise, as follows.

•Wiring length must be minimized. Do not make unnecessary

loops.

•Keep the input wires away, at least 200 mm, from power

cables and high frequency lines, or shield the input cables
with a metal plate.

•If possible, use relays at the leading in the control panel.
•For some cases, use a shielded cable or twisted-pair cable.
•Install a bleeder resistor to reduce input impedance.

(7) If dynamic scan input is configured using a DC input module and

a DC output module, in addition to the response-delay of output
and input, consider the difference of timing caused by the PLC

scan. Moreover, diodes must be installed to prevent erroneous

input caused by detour circuit, (the figure below is an example of

4X4 input)

Input module

67a oTe 6jj 6|n

:

k

Output module

:

k

^

^

"6| n

K

For example, when contact a is ON, the change timing between

output 0 and input 0 is as follows :

PLC scan cycle

-Output 0

^internal)

Output

0 (external)

Input

0 (external)

Input

0

(internal)

T1 : Output response

delay

T2: Input response

delay

Note that the change timing of output 0 and input 0 will be

affected with the scan time of the PLC and the response time of

input and output.