Oc cr – Toshiba Programmable Controller PROSEC T3 User Manual

Page 98

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

CO

■0

3D

O

CO

m

o

Part

Error message and related information

Relevant

LED displays

Meaning of the error and

countermeasures

Error message

Information

1

Information

2

Information

3

special

relay

RUN

FAULT

I/O

Program

No SFC macro entry

Program

type-
block No.

Macro No.

S0006

S0030

o

O

The macro program specified by macro
step is not programmed. Check that the
macro program has been programmed,
and that the macro No. is correct.

SFC jump label err

Program

type-
bloclr No.

SFC label
No.

S0006
S0030

o

o

The SFC label No. is duplicated. Change
the SFC label No.

No SFC jump label

Program

type-

block No.

SFC label
No.

S0006

S0030

o

o

The SFC label instruction specified by the
SFC jump instmction is not programmed.

Insert the SFC label instruction.

Duplicate SFC No.

Program
type-
block No.

SFC
program
No.

S0006
S0030

o

o

The SFC program No. is duplicated.
Change the SFC program No.

Invalid SFC prog

Program

type-

block No.

S0006

S0030

o

o

The correspondences between the initial
step and end step or SFC end, or macro
entry and macro end do not match.
Change the program so that the
correspondence match.

Illegal inst

Program

type-
block No.

Address
in the block

S0006
S0030

O

o

An illegal instruction has been detected in

the program.

After executing "Clear memory," reload the
program.

Invalid Fun inst

Program

type-
block No.

Address

in the block

FUN No.

S0006
S0030

O

o

An instruction which is not su|:^orted by
T3 has been detected. Erase the relevant
instruction.

Boundary error

Program

type-

block No.

Address
in the block

FUN No.

50064
or
50065

The operand specified by Indexed FUN

instruction has exceeded the limit. Check

the value of the index register.

Duplicate entry No.

Program

type-

block No.

Address

In the block

Entry No.

S0006
S0030

O

o

"LBL" or "SUBR" instruction is duplicated.

Check the program.

O)

o

c

cr

io

(0

3T

o

o

3

(O