Doc cooio, Installation and wiring – Toshiba Programmable Controller PROSEC T3 User Manual

Page 73

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

4. Installation and Wiring

4.6

Wiring of the power

supply

Wire the external power supply to the T3 power supply module.
When using the expansion unit, supply the power simultaneously to
the basic and expansion units.

(1 ) Power conditions

Power voltage

85 to 132 Vac/170 to 264 Vac,
50/60 Hz (PS361)

20.4 to 28.8 Vdc (PS332)

Power consumption

80 VA or less (PS361)

(per one PS)

sow

or less

(PS332)

Retentive power

10 ms or less

interruption

(2) Correctly set the voltage switch terminals of the PS361

according to the power voltage. (100 to 120 Vac: short,

200 to 240 Vac: open)

(3) Install an electrostatic shielded transformer or a noise filter if the

power contains noise. See the figure at the bottom.

(4) Use twisted-pair cables (1.25 mm^) as the power supply cable.

Keep the cable as far as possible from the I/O cables.

(5) If the expansion unit with a power supply module is used, the

power for the basic and expansion units should be supplied from

the same source. Apply power at the same time or in the order

of the expansion unit then the basic unit.

(6) If a CVCF or UPS supplies power to the T3, observe waveforms

of the power supply; the peak voltage must be more than 130V

for the 100 to 120 Vac setting or 260V for the 200 to 240 Vac

setting.

Basic unit

Noise

Yielded

filter

trasformer

*

!

Power

Doc cooiO(

[

30C

-o

--0

-OL

-ON

Expansion
unit

* Voltage switch terminals

100 to 120 Vac ... short

200 to 240 Vac ... open

* !

-o

•o

-OL

-ON

User's manual ■ Hardware

65

Advertising