Grounding of longdistance expansion, Installation and wiring – Toshiba Programmable Controller PROSEC T3 User Manual

Page 72

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

4. Installation and Wiring

Grounding of long­

distance expansion

Basic unit

Expansion unit

In principle, ground a long-distance expansion unit as shown in the

above figure. If the potential changes at the grounding point,
causing malfunctions of the T3, isolate the expansion unit from the
mounting frame, and ground it with a dedicated cable (2 mnf or
more).

Basic unit

Expansion unit

FG

_____

p

'

ili

!

Ground bar in the panel

2mm=

or more

i

Isolation

panel

Line filter ground (LG)

terminal

The LG terminal is a neutral point of the primary power supply line
filter. It can suppress the effect caused by the noise from the power

supply line, by grounding the LG terminal.

Therefore, normally, ground the LG terminal together with the FG
terminal.

However, depending on the power system, leakage current to the

ground from the LG may cause problems. In this case, install an
isolated transformer in the power line, or open the LG terminal. If

the unit Is installed in isolation, open the LG terminal.

Do not connect the LG and FG terminals without grounding them.

64

PROSEC T3