Point ac output, Specification – Toshiba Programmable Controller PROSEC T3 User Manual

Page 50

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

2. Specification

32-point AC output

Type

Category

No. of output points

Insulating method

Rated load voltage

Range of load voltage

Max. load current

Voltage drop at ON

Leakage current at OFF

Min. load current

Max. inrush current

Delay

OFF —ON

ON — OFF

Output signal display

Module status display

External connection

No. of commons

No. of output points

per common

Derating condition

Internal current

consumption

Insulation resistance

Withstand voltage

Built-in fuse

Surge suppressor

Weight

Internal circuit

AC364

Triac output

32 points, 2-word output (Y 2 W)

Photo-coupler

100 to 240 Vac (50/60 Hz)

24 to 264 Vac (47 to 63 Hz)

0.5 A/point, 3.2 A/common, 5 A/modute

1.5 V or less

0.8 mA or less (at 100 Vac, 50 Hz)

1.6 mA or less (at 200 Vac, 50 Hz)

100 mA (24 Vac), 50 mA (100 to 240 Vac)

20 A/20 ms (points and common)

1 ms or less

1 ms+1^cycle or less

LED display for all points, lit at ON, internal logic side

Fusing display LED (FL, FH), lit at fusing

38-pin removable terminal block, M3.5

2 (insulated between commons)

16 points per common

None

5 Vdc, 800 mA or less

10 MQ or less (500 Vdc)

1500 Vac, 1 minute (between commons, between

internal and external circuits)

6 A/commonX2

CR snu№er circuit

540g

42

PROSEC T3