4. installation and Wiring

Ground connection

between units

2 mm2

or more

Connect the FG terminal of the power supply module to the unit

mounting screw, and to the ground bar in the panel by 2 mmi^ or
larger wire in shortest possible distance.
Use a dedicated ground for the control circuit, and keep the

ground cable away from that for high-power systems.
100Q or less to earth is recommended.