Ground connection between units, Installation and wiring – Toshiba Programmable Controller PROSEC T3 User Manual
Page 71
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Advertising
4. installation and Wiring
Ground connection
between units
2 mm2
or more
Connect the FG terminal of the power supply module to the unit
mounting screw, and to the ground bar in the panel by 2 mmi^ or
larger wire in shortest possible distance.
Use a dedicated ground for the control circuit, and keep the
ground cable away from that for high-power systems.
100Q or less to earth is recommended.
User's manual - Hardware
63
Advertising