4. Installation and Wiring

4.1

Operating environment

Do not install the T3 in the following locations :

Where the ambient temperature drops below 0*C (32“F)

or exceeds 55‘C (13l“F)

Where the relative humidity drops below 20% or exceeds
90%

Where there is condensation due to sudden temperature
changes

Where there are vibrations that exceed the tolerance of the

T3

Where there are shocks that exceed the tolerance of the T3

Where there are corrosive or inflammable gases

(The installation location should be below 0.05 ppm of

sulfurous acid gas, below 0.01 ppm of hydrogen sulfide.)

Where there are dust, machining debris or other particles

In locations exposed to direct sunlight

Observe the following precautions when installing

enclosures for mounting the T3 :

Provide the maximum possible distance between high-

voltage or high-power panels. This distance must be at least
200 mm (8 in).

If the enclosures are installed near high-frequency

equipment, be sure to ground the enclosures correctly.

When sharing the channel base with other panels, check for

leakage currents from the other panels or equipment.

User's manual - Hardware