Point relay output, R0364, Specification – Toshiba Programmable Controller PROSEC T3 User Manual

Page 52

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

2. Specification

32-point relay output

Type

Category

Output

No. of output points

Insulating method

Rated toad voltage

Range of load voltage

Max. load current

Contact ON resistance

Leakage current at OFF

Min. load current

Delay

OFF ON

ON — OFF

Output signal display

Module status display

External connection

No. of commons

No. of output points
per common

Internal current

consumption

External

power

for relay

Rated voltage

Rated current

Voltage range

Mechanical life

Electrical contact life

insulation resistance

Withstand voltage

Built-in fuse

Weight

Internal drcuit

R0364

Electromechanical relay output

NO-contact

32 points, 2-word output (Y 2 W)

Photo-coupler

240 Vac/24 Vdc

Up to 264 Vac/125 Vdc

2 A/point (resistive load), 5 A/common

50 mQ or less (initial value)

None

5 Vdc, 10 mA (50 mW or more)

10 ms or less

10 ms or less

LED display for all points, lit at ON, internal logic side

^normal external power suF^ly display LED (F),

tit at abnormal state

38-pin removable terminal block, M3.5

4 (insulated between commons)

8 points per common

5 Vdc, 170 mA or less

24 Vdc

300 mA (24 Vdc, at all points ON)

21.6 to 26.4 Vdc

20 million times or more

See the next page

10 MQ or more (500 Vdc)

1500 Vac, 1 minute (between commons, between

internal and external circuits)

_____

None

51 Og

OCOM

44

PROSEC T3