Point isolated relay output, Specification – Toshiba Programmable Controller PROSEC T3 User Manual

Page 54

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

2. Specification

16-point isolated relay

output

Type

Category

Output type

No. of output points

Insulating method

Rated load voltage

Range of load voltage

Max. load current

Contact ON resistance

Leakage current at OFF

Min. load current

Delay

OFF - ON

ON OFF

Output signal display

Module status display

External connection

Common connection

Internal current

consumption

External
power
for relay

Rated voltage

Rated current

Voltage range

Mechanical life

Electrical contact life

Insulation resistance

Withstand voltage

Built-in fuse

Weight

Internal circuit

R0363S

Electromechanical relay output

NO-contact

16 points, 1-word output (Y 1 W)

Photo-coupler

240Vac/24Vdc

Up to 264 Vac/125 Vdc

2 A/point

50 mQ or less (initial value)

None

5 Vdc, 10 mA (50 mW or more)

10 ms or less

10 ms or less

LED di^lay for all points, lit at ON, internal logic side

^normal external power supply display LED (F),

lit at abnormal state

38-pin removable terminal block, M3.5

16-point isolated contact

5 Vdc, 100 mA or less

24 Vdc

145 mA (24 Vdc, at all points ON)

21.6 Vdc to 26.4 Vdc

20 million times or more

See the next page

10 MQ or more (500 Vdc)

1500 Vac, 1 minute (between the points, between
internal and external circuits)

None

450g

46

PROSEC T3