Precautions for i/o modules – Toshiba Programmable Controller PROSEC T3 User Manual

Page 60

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

3. Precautions for I/O Modules

(4) If the AC lines are installed in parallel with high frequency or

power lines, induced current may cause erroneous input. In this

case, take necessary countermeasures as follows:

Change the installation route of AC input lines so that

they are not parallel with power lines and high
frequency lines.

Use twisted-pair cables as input lines.

Use shielded cables as input lines.

Use relays at the leading in the control panel (the relay
must satisfy larger ON current).

Install a bleeder resistor to lower the input impedance.

(5) If the input module and an inductive load are connected in

parallel, a surge voltage generated at both-ends of the load

when the contact is changed to OFF may cause a malfunction of
the PLC. In this case, install a surge absorption element in

parallel with the load to suppress the surge voltage.

Input module

)

)

-----------------------------------------------------------

-0^

Hl-O-

----------Inductive load

^ ^ Surge absorption element (snubber circuit, etc.)

52

PROSEC T3