Lightning Protection

Shield Protection

Gas Discharge, MOV, or TVS devices may be used for the shield-to-ground protection. MOV and TVS devices
may not be used to protect the network data lines.

Suggested Gas Discharge Arresters

Three-electrode device configurations are suggested for the data network lines, as this will require the use of only
one physical device to protect both lines. The network lines should be connected to the two outside ends of the
arrester, while the middle terminal must be connected to a stable earth ground. Alternatively, two each of two-
electrode configurations may be used (contact manufacturer for details). The following table provides a list of
three-electrode Gas Discharge device manufacturers.

* Manufactures of Suggested Gas Discharge Arresters

Figure 4.8 illustrates a typical outdoor twisted pair network in which Gas Discharge arresters have been
incorporated.

Figure 4.8 Network and Shield Lightning Protection

Vendor and Configuration

Series

Model

Voltage

Sankosha, 3 Electrode
www.sankosha-usa.com/cp6htm

3YW

A

90VDC

Citel, 3 Electrode
www.citelprotection.com

BT (or BTR)

----

90VDC

Sumida, 3 Electrode
www.srcdevices.com

PMT8

----

90VDC

Outside

Shielded Twisted Pair

Inside

Building Wall

Lightning
Protector

Gas Discharge

Surge Protectors

(Typically <5pF)

Net A

Net B

Shield