Appendix B - Qualified TP/FT-10 Cable Specifications and Sources

126

FT 3120 / FT 3150 Smart Transceiver Data Book

Table B.5 Worst-Pair Near-End Crosstalk (dB) Minimum

Values are shown for information only. The minimum near-end cross talk (NEXT) coupling loss for any pair com-

bination at room temperature is to be greater than the value determined using the formula

for all frequencies in

the range of 0.772MHz-20MHz for a length of 1000 feet:

NEXT (F

MHz)

>NEXT(0.772)-15*log(F

MHz

/0.772)

16AWG/1.3mm “Generic” Cable Specifications

The specifications for the 16AWG/1.3mm Generic cable qualified by Echelon for use with TP/FT-10 networks is
presented below. The generic single twisted pair is stranded (19 x 29) with tinned copper.

Table B.6 General Specifications

Table B.7 Attenuation and Propagation Delay Characteristics

Frequency

Crosstalk db

772kHz

58

1.0MHz

56

4.0MHz

47

8.0MHz

42

10.0MHz

41

16.0MHz

38

20.0MHz

36

Specification

Minimum

Typical

Maximum

Units

Condition

DC Resistance, each
conductor

14.0

14.7

15.5

/km

20°C per ASTM D
4566

DC Resistance Unbal-
ance

5%

20°C per ASTM D
4566

Mutual Capacitance

55.9

nF/km

Per ASTM D 4566

Characteristic Imped-
ance

92

100

108

_

64kHz to 1MHz, per
ASTM D 4566

Characteristic

Minimum

Typical

Maximum

Units

Condition

Attenuation

20kHz

64kHz

78kHz

156kHz

256kHz

512kHz

772kHz

1000kHz

1.3

1.9

2.2

3.0

4.8

8.1

11.3

13.7

dB/km

20°C per ASTM D 4566

Propagation Delay

5.6

ns/m

78kHz