FT 3120 / FT 3150 Smart Transceiver Data Book

93

Interface between Smart Transceivers and the Network

The T1 and T2 signals are each brought out of the FT-X1 transformer at two different sets of pins. The T1 and T2
connections between the FT-X1 transformer and the FT Smart Transceivers can be made via either set of pins on
the FT-X1 transformer, but the connections shown in the PCB layout figures later in this chapter generally give the
best ESD transient immunity. T1 and T2 were used in FTT-10A transceiver-based designs for ESD clamping only,
but now they are also connected directly to the FT Smart Transceivers via the old RXD and TXD signals of the
Neuron Chip.

The FT-X2 transformer has only one set of T1 and T2 pins, corresponding to pins 5 and 6 on the FT-X1
transformer. Therefore, connection to FT Smart Transceivers, ESD protection circuitry, and C5/C6 capacitors are
all connected through the same set of T1 and T2 pins.

Since the T1 and T2 lines are analog connections between the FT Smart Transceiver and the FT-X1 transformer, no
other parallel connections should be made to these lines (other than the C5 and C6 capacitors and ESD protection
diodes shown in Figure 4.1), and no components should be placed in series between the FT Smart Transceiver and
the FT-X1or FT-X2 transformer. In particular, no RXD/TXD sensing circuitry should be attached to these lines.
There is now an explicit RXD/TXD signal available on the COMM_ACTIVE pin of the FT Smart Transceiver that
can be used for the purpose of driving RXD and TXD LEDs, if desired. See the following section for more
information about the COMM_ACTIVE LED drive circuit.

Interface between Smart Transceivers and the

Network

The preferred interconnection between the FT-X1 or FT-X2 transformer, an FT Smart Transceiver, and the
associated transient protection circuitry is shown in Figure 4.1. When using the FT-X1 transformer, pins 3 and 4 are
connected to the Smart Transceiver as shown in the figure, while ESD protection diodes are connected to pins 5
and 6. The FT-X2 transformer does not have pins 3 and 4. Connections to the Smart Transceiver and to the ESD
protection on FT-X2 are both done via pins 5 and 6. Figure 4.1 is not a complete schematic, since it does not
include the clock, reset, and power supply bypass circuits for the FT Smart Transceivers. Refer to the FT 3120 and
FT 3150 Smart Transceiver Datasheet
for this additional information.

Figure 4.1 FT Smart Transceiver and FT-X1 or FT-X2 Interconnections with Transient Protection
Circuitry

C1

D2

+5V

D1

NET1

NET2

See

Text

C3

C4

VR1

NET_A

NET_B

T1
T2

T1

T2

FT-X1 or FT-X2

Transformer*

T1

T2

RTMP

COMM_ACTIVE

FT 3120 Transceiver
FT 3150 Transceiver

(Partial)

3
4

+5V

Optional

COMM_ACTIVE

LED Drive Circuit

2

1

5

6

SLEEP

D3

D4

D5

D6

C5

C6

See

Text

*Use pins 5 & 6 for FT-X2