Leveldetect input – Echelon FT 3150 Smart Transceiver User Manual

Page 49

Advertising
background image

FT 3120 / FT 3150 Smart Transceiver Data Book

43

Direct I/O Objects

Leveldetect Input

Pins IO0 – IO7 may be individually configured as leveldetect input pins, which latch a negative-going transition of
the input level with a minimal low pulse width of 200ns, with a FT Smart Transceiver clocked at 10MHz. The
application can therefore detect short pulses on the input which might be missed by software polling. This is useful
for reading devices, such as proximity sensors. This is the only direct I/O object which is latched before it is
sampled.
The latch is cleared during the when statement sampling and can be set again immediately after, if another
transition should occur. See Figure 3.11.

Figure 3.11 Leveldetect Input Latency Values

Symbol

Description

Typ @ 10MHz

t

fin

Function call to sample

IO0
IO1
IO2
IO3
IO4
IO5
IO6
IO7

35 µs
39.4 µs
43.9 µs
48.3 µs
52.7 µs
57.2 µs
61.6 µs
66 µs

t

ret

Return from function

32 µs

1ST NEGATIVE

TRANSITION

IS LATCHED

200ns

SYSTEM

CLOCK

(@ 10MHz)

t

ret

t

fin

TIME

INPUT

LATCH

SAMPLED

AND THEN

CLEARED

END OF
io_in()

START OF

io_in()

INPUT

PIN

IO10

IO9

IO8

IO0

IO1

IO2

IO3

IO4

IO5

IO6

Optional Pull-Up Resistors

IO7

2ND
NEGATIVE
TRANSITION
IS LATCHED

INPUT

LATCH