Chapter 5 - Network Cabling and Connections

114

FT 3120 / FT 3150 Smart Transceiver Data Book

Only one LPI-10 interface is supported per segment. The LPI-10 contains the two required terminators. The other
terminator must be an RC-type (see figure below).

Figure 5.6 Twisted Pair Termination Network

Grounding Shielded Twisted Pair Cable

When using shielded twisted pair, terminate the twisted pair and ground the cable shield, as shown in Figure 5.7.

Figure 5.7 Terminating and Grounding Shielded Twisted Pair Cable

The twisted pair is terminated according to the guidelines listed in the previous sections. The cable shield should be
grounded using a capacitor to tie the shield to earth ground, and a large-value resistor to bleed off any static charge on
the shield.

Tie the shield to earth ground through a capacitor, instead of a direct connection, in order to avoid DC and 50/60 Hz
ground paths from being formed through the shield. Typical values for Rb and Cc are as follows:

Cc = 0.1

µF, 10%, Metalized Polyester, ≥ 100V

Rb = 470k

Ω, 1/4W, ±5%

The cable shield should be grounded at least once per segment, and preferably at each device.

Unshielded

Twisted Pair

(UTP)

Ra

Ca

100µF

50Vmin

Cb

100µF

50Vmin

+

+

Notes:

Ca and Cb are typically aluminum-electrolytic
type for improved longevity in the presence of
ESD – observe polarity.

Shielded

Twisted Pair

(STP)

Ca

100µF

50Vmin

Rb

Cc

Cb
100µF
50Vmin

Ra

Twisted Pair

Termination Circuit

Shield

Grounding

Circuit