12

9437200990 Rev C

Main Analog Meter, Redundant Analog Meter, and Supervisory Analog Meter Buttons

Pressing one of these Metering Index screen buttons (if so equipped) accesses the corresponding
metering page which displays the parameters illustrated in Figure 9. (Only the Main Meter Panel is shown
here; the Redundant and Supervisory Meter Panels are similar.) The value of each parameter is
graphically shown on an analog scale and also displayed in digital format. The minimum and maximum
values established on the Analog Meter Configuration screen determine the metering ranges shown on
this screen.

Figure 9. Main Meter Panel

Gen Analog Meter Config Button

Pressing this Metering Index screen button accesses the Generator Metering Configuration screen
(Figure 10) which sets the range of the generator metering values displayed on the Generator Metering
screen. The generator power factor metering range is fixed so no adjustment is provided. The minimum
and maximum value for a metered parameter is changed by pressing the corresponding value. This
displays a keypad which is then used to assign the desired metering limit. Pressing the Enter (ENT)
button saves the value. Minimum and maximum metering parameter ranges are listed in Table 2.

Table 2. Metering Parameter Ranges

Parameter

Minimum

Maximum

Field Current

0

10000

Field Voltage

–1500

1500

Generator Current

0

30000

Generator Voltage

0

30000

Generator Megavars

–1500

1500

Generator Megawatts

0

1500

IDP-1200 Operation with ECS2100 and ECS/RW