MEL or the UEL curve. The horizontal capability curve screen is shown in Figure 65. A vertical curve is
also available.

Figure 65. Capability Curve Screen

Task Guide

Table 7 lists common tasks along with the IDP-1200 pages that provide the controls for performing the
tasks.

Table 7. Tasks and Screens Cross-Reference

Task

Screen

Close ac breaker

Control

Flash the field

N/A, field is flashed automatically
when ac field breaker is closed.

Place regulator in Auto or Manual
mode

Control

Raise or lower voltage

Control
Var

Change the controlling channel

Transfer Control

Change Local/Remote control

Control

View alarms

Any page

Acknowledge alarms

Alarm/Fault – Active
Alarm/Fault – History

Password Settings

The default, level 2 password is “4321”. Use the following procedure to change the security password. A
USB flash drive is required to change the password.

1.

Create a CSV (comma-separated values) file named “Security.csv” that has its content structured
as shown in Table 8. Place the new password where “New” is shown in the table. Passwords are

IDP-1200