Transfer control, Power system stabilizer – Basler Electric IDP-1200 User Manual

Page 58

Advertising
background image

50

9437200990 Rev C

Transfer Control

This screen (Figure 55) is used to transfer control from one control system channel to another.

When transferring control system channel control, observe the following:

The IDP-1200 being used must be in control.

You must know whether the IDP-1200 being used is Local or Remote (as displayed on the
Local/Remote indicator). Note that the IDP-1200 located on the control system equipment
enclosure is considered as the Local IDP-1200. An IDP-1200 at any other location is considered
to be a Remote IDP-1200.

Level 1 password access is required (through use of the Log In button).

The redundant channel tracks the output of the main channel and displays the percent difference
(error) between the outputs of the redundant and main channels.

To transfer control system channel control:

1.

Ensure that the Enable Transfer indicator shows “Panel Transfer Enabled”. This is achieved by
pressing the Enable Transfer button.

2.

Press the Transfer indicator button and select the desired channel.

Figure 55. Transfer Control Screen

Power System Stabilizer

This page (Figure 56) displays power system stabilizer operating status and enables/disables PSS
operation. PSS metering indications for each control system channel are displayed. The PSS output for
the active channel is displayed adjacent to the Channel in Control indicator.

IDP-1200 Operation with DECS-2100 and DECS/RW